ODF:1/4; Flow cooling capacity(KW) under pressure drop△p(1 2)=0.07bar; R134a:13.3; R22/R410A:14.7; R407C:14.4; R404A/R507:10.8; R502:10.5; Dimensions(mm):A:18; B:118; D:76; L:154;
ODF:1/4;
Flow cooling capacity(KW) under pressure drop△p(1 2)=0.07bar;
R134a:13.3;
R22/R410A:14.7;
R407C:14.4;
R404A/R507:10.8;
R502:10.5;
Dimensions(mm):A:18; B:118; D:76; L:154;
Remark:
1: Capacity to work status: liquid refrigerant temperature tc= 30°C, saturated evaporation temperature=-15"C,the pressure drop△p=0.07bar
2: It is not recommended used when pressure drop△p over than 0.14 bar