ODF: 3/8;Flow cooling capacity(KW) under pressure drop△p(1 2)=0.07bar, R134a:10.5, R22/R410A:11.5, R407C:11.2, R404A/R507:7.8, R502:7.4; Dimensions(mm):A:19; B:66; D:42; L:104;
ODF: 3/8;
Flow cooling capacity(KW) under pressure drop△p(1 2)=0.07bar;
R134a:10.5;
R22/R410A:11.5;
R407C:11.2;
R404A/R507:7.8;
R502:7.4;
Dimensions(mm):A:19; B:66; D:42; L:104;
Remark:
1: Capacity to work status: liquid refrigerant temperature tc= 30°C,saturated evaporation temperature=-15"C,the pressure drop△p=0.07bar
2: It is not recommended used when pressure drop△p over than 0.14 bar